High-Voltage Static Var Generator 6-35kV

High-voltage static var generator for 6 kV to 35 kV distribution. A chain-link IGBT converter supplies or absorbs ±0.3 to ±20 Mvar of reactive power within 5 ms, holding power factor, busbar voltage and flicker at the point of common coupling.  

Description

The KLD-SVG high-voltage static var generator is a dynamic reactive power compensation and harmonic mitigation device for 6-35kV power systems. It is a static synchronous compensator (STATCOM) built on chain-link IGBT converter technology: it supplies or absorbs reactive power continuously, without switching steps and without the mechanical delay of a contactor, so busbar voltage holds steady while the load moves. Because the output is a controlled current rather than a switched susceptance, the device keeps compensating when the voltage sags, absorbs reactive power from lightly loaded cable networks, corrects negative-sequence current from unbalanced loads, damps voltage flicker and filters part of the load harmonic current. Typical installations are steel mills, wind farm collector substations, railway traction feeds, large rectifier plants and arc furnace shops, where a capacitor bank is either too slow or too coarse for the job.

Principle

An SVG belongs to the FACTS family, flexible AC transmission systems. Where an SVC switches passive branches in and out of circuit, an SVG synthesises the voltage it needs and lets the current follow. Coupled to the busbar through a step-up transformer or a reactor, it works as a controllable reactive current source: no moving parts, no switching steps, and no capacitor bank to age.

How a chain-link STATCOM works

  • ● Current and voltage transformers measure the system and pass the signals to a conditioning module. A DSP calculates the required compensation at high speed, and a self-commutated bridge built from fully controllable high-power semiconductor devices generates the current.
  • ● The controller adjusts the magnitude and phase of the converter's AC-side output voltage. Above system voltage the device exports leading current, below it draws lagging current, and matched to system voltage it idles. Reactive output is continuous in both directions, and the move from full capacitive to full inductive takes milliseconds.
  • ● The main circuit uses a cascaded, or chain-link, inverter topology: several low-voltage power modules stacked per phase, each switching at a modest frequency, with the whole stack producing a near-sinusoidal output and keeping total current distortion below 3%.
  • ● Every power module carries a built-in mechanical bypass. When one fails it is shorted out of the chain and the unit keeps running at reduced capacity, which is the basis of the automatic N-1 and N-2 redundancy.
SVG device principle diagram: converter, DC capacitor, coupling transformer and equivalent reactance between device voltage and system voltage

No-load, capacitive and inductive operation

  • ● No-load mode: converter output voltage equals the system voltage, no current flows and no reactive power is exchanged with the grid.
  • ● Capacitive mode: converter output voltage is higher than the system voltage, leading current flows out, and the SVG behaves as a capacitor whose susceptance can be adjusted continuously.
  • ● Inductive mode: converter output voltage is lower than the system voltage, lagging current is drawn in, and the SVG behaves as an adjustable reactor.
  • ● Both directions are available without switching hardware, so the same unit can correct an inductive plant through the day and absorb the capacitive charging current of a lightly loaded cable network at night.
SVG device basic principle table comparing no-load, capacitive and inductive operation modes with waveform and current direction

Advantages

1

Fast response, 5 ms

Advanced DC-side voltage balancing control gives a dynamic response of up to 5 ms, fast enough to suppress voltage fluctuation and flicker rather than report on it afterwards.

2

Four control modes

Constant device-side reactive power, constant system-side power factor, constant system-side voltage and load compensation, plus a combined mode where a site needs more than one.

3

Zero steady-state error

Built on instantaneous reactive power theory, the reactive power loop settles without a residual offset, and the DC voltage balancing method keeps every power module in step.

4

Comprehensive protection

Overcurrent, overvoltage, undervoltage, overtemperature, short circuit, communication failure and transmission fault protection, backed by digital quantitative analysis and online self-diagnostics.

5

Reliable IGBT triggering

Dedicated drive circuits and laminated copper busbars carry the high-frequency switching current. The chain-link structure is phase independent and module status is uploaded in real time.

6

N+1 and N+2 redundancy

The redundant main circuit keeps the device in service through a module fault, and holds steady instead of oscillating when system conditions change, which removes the resonance risk of a badly sized SVC.

7

Strong anti-interference

Good electromagnetic compatibility, with triggering and monitoring units designed independently per phase so operation stays fast under electrical noise.

8

Output independent of busbar voltage

Reactive current does not fall away as voltage sags. A capacitor bank delivers least exactly when the voltage is low, because its output follows the square of voltage; the SVG behaves as a current source and keeps compensating.

9

Low harmonic output

The multilevel chain-link topology keeps total current distortion of the output below 3%, and the active filtering function monitors and mitigates system harmonics in real time.

10

Bidirectional compensation

Output moves smoothly from full inductive to full capacitive without switching transient, which suits welding, rolling mill and traction loads where reactive demand reverses within a cycle.

11

Efficiency above 98%

Against a TCR of the same capacity, system losses fall by 50%; against an MCR of the same capacity, by 30%.

12

20% short-term overload

Rated capacity plus 20% is available for short overloads, which covers the surge when a large motor group starts.

13

Half the footprint of an SVC

An SVG occupies roughly 50% of the space an SVC of the same rating needs, which often decides the question in a retrofit where the electrical room is already full.

14

Industrial-grade data storage

Data logging, waveform recording and fault query, with power-loss data protection so records survive an interruption. Useful when a fault has to be explained to a utility rather than to a colleague.

15

Real-time multitasking system

The platform handles avalanche events without dropping control, and the modular function-code architecture keeps configuration and maintenance short.

16

Standard communication interfaces

RS485 and Ethernet for host computer communication, integration with substation automation systems, and real-time upload of operating status to a supervisory platform.

17

Local HMI

An LCD interface with Chinese and English selectable, showing operating status and fault alarms, and recording them automatically.

Parameter

Performance indicators

Rated voltage 6kV, 10kV, 35kV
Control power supply 380V AC; 220V DC
System frequency 50Hz
Rated capacity ±0.3Mvar ~ ±20Mvar
Reactive tracking deviation ≤2%
Response time <5ms
Total current distortion of output current <3%
Efficiency >98%
Reactive power regulation method Bidirectional continuous smooth regulation
Communication interface RS485, etc.
Parallel method Support parallel connection of multiple machines
Ingress protection IP40 (customizable)

Applicable environment and installation

Storage temperature −40℃ ~ +70℃
Ambient temperature −35℃ ~ +40℃
Relative humidity Monthly average ≤90% (25℃), no condensation
Altitude ≤2000m
Seismic design intensity degree 8
Installation category Indoor cabinet / Outdoor container
Installation inclination angle <5°
Parameter
 
  • Rated voltage: 6kV, 10kV, 35kV Control power supply: 380V AC; 220V DC System frequency: 50Hz Rated capacity: ±0.3Mvar ~ ±20Mvar Reactive tracking deviation: ≤2% Response time: <5ms Total current distortion of output current: <3% Efficiency: >98% Reactive power regulation method: Bidirectional continuous smooth regulation Communication interface: RS485, etc. Parallel method: Support parallel connection of multiple machines Ingress protection: IP40 (customizable)
 
  • Storage temperature: −40℃ ~ +70℃ Ambient temperature: −35℃ ~ +40℃ Relative humidity: Monthly average ≤90% (25℃), no condensation Altitude: ≤2000m Seismic design intensity: degree 8 Installation category: Indoor cabinet / Outdoor container Installation inclination angle: <5°

Model Selection

The model code carries the full specification, so a quotation can be read off the label. Reading KLD-SVG-10-10KV-AI left to right:

  • ●KLD — Tysen-KLD
  • ●SVG — device type, high-voltage static var generator
  • ●10 — total capacity in Mvar
  • ●10KV — system voltage
  • ●A / W — air cooling / liquid cooling
  • ●I / O — indoor cabinet / outdoor container

Note: liquid-cooled SVG is the specification for harsh windy and sandy environments, high altitude, high condensation and high salt mist corrosion.

KLD-SVG main model and specification table

Specification Model Total Capacity (Mvar) System Voltage (kV) Cooling Method Installation Method
KLD-SVG-0.5-10KV-AI 0.5 10 Air Cooling Indoor Cabinet
KLD-SVG-1-10KV-AI 1 10 Air Cooling Indoor Cabinet
KLD-SVG-2-10KV-AI 2 10 Air Cooling Indoor Cabinet
KLD-SVG-2-10KV-WI 2 10 Liquid Cooling Indoor Cabinet
KLD-SVG-5-10KV-AI 5 10 Air Cooling Indoor Cabinet
KLD-SVG-5-10KV-WI 5 10 Liquid Cooling Indoor Cabinet
KLD-SVG-10-10KV-AI 10 10 Air Cooling Indoor Cabinet
KLD-SVG-10-10KV-WI 10 10 Liquid Cooling Indoor Cabinet
KLD-SVG-15-10KV-AI 15 10 Air Cooling Indoor Cabinet
KLD-SVG-15-10KV-WI 15 10 Liquid Cooling Indoor Cabinet
KLD-SVG-10-10KV-AO 10 10 Air Cooling Outdoor Container
KLD-SVG-10-10KV-WO 10 10 Liquid Cooling Outdoor Container
KLD-SVG-20-10KV-AO 20 10 Air Cooling Outdoor Container
KLD-SVG-20-10KV-WO 20 10 Liquid Cooling Outdoor Container

Note: only part of the range is listed above. For 6kV and 35kV systems, other capacities or parallel operation, contact Tysen-KLD with the system voltage and the required Mvar.

Model Selection
 
  • KLD — Tysen-KLD SVG — device type, high-voltage static var generator 10 — total capacity in Mvar 10KV — system voltage A / W — air cooling / liquid cooling I / O — indoor cabinet / outdoor container
 
  • Total capacity (Mvar): 0.5 System voltage (kV): 10 Cooling method: Air Cooling Installation method: Indoor Cabinet
 
  • Total capacity (Mvar): 1 System voltage (kV): 10 Cooling method: Air Cooling Installation method: Indoor Cabinet
 
  • Total capacity (Mvar): 2 System voltage (kV): 10 Cooling method: Air Cooling Installation method: Indoor Cabinet
 
  • Total capacity (Mvar): 2 System voltage (kV): 10 Cooling method: Liquid Cooling Installation method: Indoor Cabinet
 
  • Total capacity (Mvar): 5 System voltage (kV): 10 Cooling method: Air Cooling Installation method: Indoor Cabinet
 
  • Total capacity (Mvar): 5 System voltage (kV): 10 Cooling method: Liquid Cooling Installation method: Indoor Cabinet
 
  • Total capacity (Mvar): 10 System voltage (kV): 10 Cooling method: Air Cooling Installation method: Indoor Cabinet
 
  • Total capacity (Mvar): 10 System voltage (kV): 10 Cooling method: Liquid Cooling Installation method: Indoor Cabinet
 
  • Total capacity (Mvar): 15 System voltage (kV): 10 Cooling method: Air Cooling Installation method: Indoor Cabinet
 
  • Total capacity (Mvar): 15 System voltage (kV): 10 Cooling method: Liquid Cooling Installation method: Indoor Cabinet
 
  • Total capacity (Mvar): 10 System voltage (kV): 10 Cooling method: Air Cooling Installation method: Outdoor Container
 
  • Total capacity (Mvar): 10 System voltage (kV): 10 Cooling method: Liquid Cooling Installation method: Outdoor Container
 
  • Total capacity (Mvar): 20 System voltage (kV): 10 Cooling method: Air Cooling Installation method: Outdoor Container
 
  • Total capacity (Mvar): 20 System voltage (kV): 10 Cooling method: Liquid Cooling Installation method: Outdoor Container

Note: only part of the range is listed above. For 6kV and 35kV systems, other capacities or parallel operation, contact Tysen-KLD with the system voltage and the required Mvar.

 