KLD-AMS Series Active Filter
Ensuring high power quality of industrial and commercial facilities, helping users in various industries to solve the thorny problem of harmonic interference in the power distribution system.
With the widespread application of nonlinear power electronic devices, harmonic pollution has become an increasingly prominent issue in power systems. Nonlinear loads are major sources of harmonics, whose orders and magnitudes vary dynamically with load conditions and system operating states. As a result, traditional passive filtering technologies often struggle to meet the demands of dynamic harmonic compensation.
The KLD Active Harmonic Filter provides an effective solution through advanced, high-speed dynamic compensation technology, enabling the suppression of a wide range of harmonics. It is suitable for various applications involving harmonic pollution, particularly those with rapidly fluctuating loads. Featuring fast response, a wide filtering range, high filtering effectiveness, and low sensitivity to system parameters, the KLD AHF helps improve power quality, reduce power losses in the grid, enhance power supply efficiency, and increase the available capacity of existing power systems. It is an ideal solution for comprehensive harmonic mitigation.
The Active Harmonic Filter (AHF) is connected in parallel with harmonic-generating loads and rapidly injects compensating currents equal in magnitude and opposite in phase to the harmonic currents generated by these loads. This effectively cancels harmonic components, reducing harmonic distortion in the system’s voltage and current waveforms.
Featuring adaptive compensation, the device automatically tracks and compensates for harmonics with varying frequencies and magnitudes, responding rapidly to changing compensation demands to maintain effective harmonic suppression.



Quickly tracks fast‑changing nonlinear industrial loads.
Realizes 2nd ~ 50th‑order harmonic filtering, fully meets international standard requirements.
Per‑phase independent output for 100 % unbalance‑load compensation.
Bidirectional seamless dynamic reactive‑power compensation from inductive to capacitive
Harmonic‑only / harmonic + reactive‑power / harmonic+imbalance correction mode selectable on site.
Multiple units parallel connection for capacity expansion,Maximum 8 modules parallel under single touch‑screen for flexible capacity expansion.
Avoids resonance hazard of passive filter schemes.
Overvoltage, undervoltage, overtemperature, overcurrent, short circuit, phase-sequence abnormalities, and more than 20 additional protection functions.



| Input | |
| Operating voltage | 200~690V |
| Operating frequency | 50/60±10%Hz |
| Performance index | |
| Filtering capacity | Up to 97% |
| Filtering range | 2nd-71st harmonic |
| Full response time | ≤10ms |
| Power factor correction | Supported, configurable |
| IGBT Frequency | 20kHz |
| Overload protection | Automatic current limiting at 100% of rated output |
| Interface module | |
| Display interface | New full-color display, real-time display of system harmonics and harmonic current produced by equipment |
| Operation interface | LCD intelligent operation unit |
| Language | Simplified Chinese/English |
| Communication interface | RS485/RS232 |
| Environmental operation | |
| Ambient temperature | -10℃~+55℃ |
| Storage temperature | -40℃~+75℃ |
| Relative humidity | Maximum 95%RH (no condensing) |
| Altitude | ≤1500 meters; between 1500-4000 meters, the power decreases by 1% for every 100m increase |
Input
Operating voltage: 200~690V
Operating frequency: 50/60±10%Hz
Performance index
Filtering capacity: Up to 97%
Filtering range: 2nd-71st harmonic
Full response time: ≤10ms
Power factor correction: Supported, configurable
IGBT Frequency: 20kHz
Overload protection: Automatic current limiting at 100% of rated output
Interface module
Display interface: New full-color display, real-time display of system harmonics and harmonic current produced by equipment
Operation interface: LCD intelligent operation unit
Language: Simplified Chinese/English
Communication interface: RS485/RS232
Environmental operation
Ambient temperature: -10℃~+55℃
Storage temperature: -40℃~+75℃
Relative humidity: Maximum 95%RH (no condensing)
Altitude: ≤1500 meters; between 1500-4000 meters, the power decreases by 1% for every 100m increase
| Model | Rated Compensation Current(A) | Rated voltage(V) | Type | Cooling method |
| Three-phase three-wire system | ||||
| KLD-AMS25-3L-400V-HD | 25 | 400 | Wall-mounted, with screen | Forced air-cooling |
| KLD-AMS50-3L-400V-RD | 50 | 400 | Rack-mounted, with screen | Forced air-cooling |
| KLD-AMS100-3L-400V-RC | 100 | 400 | Rack-mounted, centralized monitoring and control | Forced air-cooling |
| KLD-AMS150-3L-400V-RC | 150 | 400 | Rack-mounted, centralized monitoring and control | Forced air-cooling |
| Three-phase four-wire system | ||||
| KLD-AMS25-4L-400V-HD | 25 | 400 | Wall-mounted, with screen | Forced air-cooling |
| KLD-AMS50-4L-400V-RD | 50 | 400 | Rack-mounted, with screen | Forced air-cooling |
| KLD-AMS100-4L-400V-RC | 100 | 400 | Rack-mounted, centralized monitoring and control | Forced air-cooling |
| KLD-AMS150-4L-400V-RC | 150 | 400 | Rack-mounted, centralized monitoring and control | Forced air-cooling |
Three-phase three-wire system
Rated Compensation Current(A):25
Rated voltage(V):400
Type:Wall-mounted, with screen
Cooling method:Forced air-cooling
Rated Compensation Current(A):50
Rated voltage(V):400
Type:Rack-mounted, with screen
Cooling method:Forced air-cooling
Rated Compensation Current(A):100
Rated voltage(V):400
Type:Rack-mounted, centralized monitoring and control
Cooling method:Forced air-cooling
Rated Compensation Current(A):150
Rated voltage(V):400
Type:Rack-mounted, centralized monitoring and control
Cooling method:Forced air-cooling
Three-phase four-wire system
Rated Compensation Current(A):25
Rated voltage(V):400
Type:Wall-mounted, with screen
Cooling method:Forced air-cooling
Rated Compensation Current(A):50
Rated voltage(V):400
Type:Rack-mounted, with screen
Cooling method:Forced air-cooling
Rated Compensation Current(A):100
Rated voltage(V):400
Type:Rack-mounted, centralized monitoring and control
Cooling method:Forced air-cooling
Rated Compensation Current(A):150
Rated voltage(V):400
Type:Rack-mounted, centralized monitoring and control
Cooling method:Forced air-cooling